Answer:
Please ensure that there is no obstruction near the air outlets, as obstructions will cause freshly blown air to be sucked back into the return air outlets, making the temperature sensor mistakenly suppose that the room temperature has reached the set temperature and stop the compressor. However, the compressor will start again when the room temperature changes, resulting in repeated starting noises.
Advice:
Remove the obstruction.